INVERTER DC - AC Power Supply

 


INV-1200 and INV-1210
DC/AC Inverter, produces  AC Power from your DC source or Battery bank

INV1200

 

Behlman's INV series, INVERTERS deliver 1200 VA of 120 Vac, 60 Hz power in a 3.5 inc. high rack mount chassis. The Inverters operate from either 48 Vdc, 125 Vdc or 250VDC. You have a choice of a low distortion, sinewave output, Model INV1200 or a well regulated quasi-sinewave output, Model INV1210.

  

FEATURES

  • 1200 VA in a 3.5" high chassis

  • Sinewave or Quasi-Sinewave Output, Isolated and Floating

  • 100% of Rated Power into any Power Factor Load.

  • Crest Factor, 3:1

  • Excellent Line & Load Regulation

  • Custom output frequencies for frequency converter / frequency conversion applications (consult factory).

  • Option Bypass, DC to AC with Alarms and Indicators or AC to DC.

 

  Click here for PrintableSpecifications Sheet.


SPECIFICATIONS

INPUT

MODELS 

INV-1200-48 

INV-1210-48 

INV-1200-125 

INV-1210-125 

INV-1200-250
INPUT 48 VDC +/- 20%
125 VDC +/- 20%
250 VDC +/- 20%
 
  • Quiescent DC current drain less than: 2 Amps @ 48 VDC,
                                                            1 Amp @ 125 VDC,
                                                            0.5 Amps @ 250 VDC. 

  • Maximum DC burden (full load):        40 Amps DC @ 38 VDC,
                                                          15 Amps DC @ 100 VDC,
                                                          7.5 Amps DC @ 200 VDC.

  • Connections: Barrier type terminals on the rear.

 

OUTPUT

Voltage:
120 VAC +/- 5%, 60 Hz isolated
Current:
10 Amps
Power:
1200VA
Waveform:
Sine Wave Output (Model INV1200)
Modified Sine Wave Output (Model INV1210)
Power Factor:
100% of rated output into any power factor load.
Distortion:
< 3% THD typical ( Model INV1200 )
Efficiency:
80-85% typical
Connection:
Two NEMA 5-15 receptacles. Option -TB:  Barrier terminals.

 

PROTECTION CIRCUITS

Input:
Main circuit breaker, Option i: Fuse.
Short Circuit Protection:
Short circuit overload electronically latches output to protect load.
Thermal Protection:
Internal temperature sensor prevents heat damage.

 

FRONT PANEL CONTROLS and INDICATORS

Power On/Off circuit breaker
Three LED's:  DC IN, AC IN, AC OUT . ( With Option D1 or A1 )

 

MECHANICAL SPECIFICATIONS

Dimensions:
High strength table top chassis, 3.5"H x 17.00"W x 17.00"D.
Weight:
25 lbs, Option

 

ENVIRONMENT SPECIFICATIONS

Operating Temperature:
-20 to 55 C.
Humidity:
Up to 95% non-condensing
SWC:
Designed to meet IEEE C37.90.1.
Fast Transient:
Designed to meet IEEE C37.90.1.
EMI:
Designed for immunity to conducted & radiated EMI.
RFI:
Designed to meet IEEE C37.90.2 - 1997.

 

OPTIONS

D1
AC Input, with Indicators and Alarms.
DC input primary. Includes AC input with "Transfer Circuit" to switch from DC input to AC input, in 300msec. typical, upon loss of DC input or Inverter. Includes AC fuse, (3) indicators and (3) form "C" contacts for AC IN, DC IN and Inverter ON.
A1
Same as Option D1 except AC Mains is primary input with "Transfer" to DC input upon loss of AC.
TB
Barrier strip on rear in place of NEMA 5-15 receptacles

West Coast

2363 Teller Road / Suite 108,
Newbury Park, CA 91320
TEL (800) 456-2006 - (805) 375-7046
FAX (805) 498-2147

Headquarters:

80 Cabot Court.,
Hauppauge, NY 11788
TEL (800) 874-6727 - (631) 435-0410
FAX (631) 951-4341 * E-mail: sales@behlman.com

Easy Payment, We accept:
MasterCard, Visa, Discover,
American Express

About Behlman | Select a Product | Catalog Request | Support | GSA | Sales/Reps | Orbit Int'l | Home
AC Power Supply/Frequency Converter: Switching | Inverters | UPS | Modified Standard Products
COTS: AC-DCDC-DC | Railroad Signal Source | New Products | Application Notes | Wild Frequency Information Center